Product comparison · 2 power distribution units (pdus)

APC Rack PDU, Metered, 2U, 30A, 120V, (16) 5-20 vs APC Rack PDU, Switched, ZeroU, 5.7kW, 120V

Add a product
  • 15specifications compared
  • 12differ
  • 3identical
  • 2known for one product only

Key differences

  • Input connection type
    • Rack PDU, Metered, 2U, 30A, 120V, (16) 5-20:NEMA L5-30P
    • Rack PDU, Switched, ZeroU, 5.7kW, 120V:NEMA L21-20P
  • Output connections
    • Rack PDU, Metered, 2U, 30A, 120V, (16) 5-20:16x NEMA 5-20R
    • Rack PDU, Switched, ZeroU, 5.7kW, 120V:24x NEMA 5-20R
  • Cable length
    • Rack PDU, Metered, 2U, 30A, 120V, (16) 5-20:3.66 m
    • Rack PDU, Switched, ZeroU, 5.7kW, 120V:3.05 m
  • Nominal input voltage
    • Rack PDU, Metered, 2U, 30A, 120V, (16) 5-20:120 V
    • Rack PDU, Switched, ZeroU, 5.7kW, 120V:208 V
  • Load capacity
    • Rack PDU, Metered, 2U, 30A, 120V, (16) 5-20:2880 VA
    • Rack PDU, Switched, ZeroU, 5.7kW, 120V:5700 VA
  • Maximum input current per phase
    • Rack PDU, Metered, 2U, 30A, 120V, (16) 5-20:30 A
    • Rack PDU, Switched, ZeroU, 5.7kW, 120V:20 A
  • Operating temperature (T-T)
    • Rack PDU, Metered, 2U, 30A, 120V, (16) 5-20:-5 - 45 °C
    • Rack PDU, Switched, ZeroU, 5.7kW, 120V:0 - 45 °C
  • Width
    • Rack PDU, Metered, 2U, 30A, 120V, (16) 5-20:444 mm
    • Rack PDU, Switched, ZeroU, 5.7kW, 120V:56 mm

Side by side

Differences highlightedShow differences only (on)
Comparison of Rack PDU, Metered, 2U, 30A, 120V, (16) 5-20, Rack PDU, Switched, ZeroU, 5.7kW, 120V
17 specifications
Ports & interfaces2 differ
Input connection typeDiffersNEMA L5-30PNEMA L21-20P
Output connectionsDiffers16x NEMA 5-20R24x NEMA 5-20R
Features1 differ
Cable lengthDiffers3.66 m3.05 m
Power3 differ
Nominal input voltageDiffers120 V208 V
Load capacityDiffers2880 VA5700 VA
Maximum input current per phaseDiffers30 A20 A
Maximum total current draw per phaseKnown for one24 AUnknown — not stated by the source
Certificates1 differ
CertificationDifferscUL Listed,CSA,FCC Part 15 Class A,ICES-003,UL 60950,UL Listed, RoHScUL Listed,CSA,FCC Part 15 Class A,ICES-003,Industry Canada,UL 60950,UL Listed
Operational conditions1 differ
Operating temperature (T-T)Differs-5 - 45 °C0 - 45 °C
Weight & dimensions4 differ
WidthDiffers444 mm56 mm
DepthDiffers112 mm44 mm
HeightDiffers88 mm1619 mm
WeightDiffers3.36 kg5.91 kg
Designidentical
Product colourKnown for oneUnknown — not stated by the sourceBlack

A dash means the value is not stated by the source. Unknown values are never counted for or against a product, and there is no overall score.