Product comparison · 2 power distribution units (pdus)

Vertiv MPH2 Rack PDU, branch metered, 0U, input IEC 60309 vs Vertiv MPH2 Rack PDU, receptacle managed, 0U, input Anschlussblock 230/400V

Add a product
  • 20specifications compared
  • 6differ
  • 14identical
  • 1known for one product only

Key differences

  • PDU types
    • MPH2 Rack PDU, branch metered, 0U, input IEC 60309:Metered
    • MPH2 Rack PDU, receptacle managed, 0U, input Anschlussblock 230/400V:Metered, Switched
  • AC outlets quantity
    • MPH2 Rack PDU, branch metered, 0U, input IEC 60309:19 AC outlet(s)
    • MPH2 Rack PDU, receptacle managed, 0U, input Anschlussblock 230/400V:18 AC outlet(s)
  • Output connections
    • MPH2 Rack PDU, branch metered, 0U, input IEC 60309:17 x C13 & 2 x C19
    • MPH2 Rack PDU, receptacle managed, 0U, input Anschlussblock 230/400V:6 x C13 & 12 x C19
  • Nominal input voltage
    • MPH2 Rack PDU, branch metered, 0U, input IEC 60309:230 V
    • MPH2 Rack PDU, receptacle managed, 0U, input Anschlussblock 230/400V:230-400 V
  • Maximum current
    • MPH2 Rack PDU, branch metered, 0U, input IEC 60309:16 A
    • MPH2 Rack PDU, receptacle managed, 0U, input Anschlussblock 230/400V:32 A
  • Height
    • MPH2 Rack PDU, branch metered, 0U, input IEC 60309:916.5 mm
    • MPH2 Rack PDU, receptacle managed, 0U, input Anschlussblock 230/400V:1736.5 mm

Side by side

Differences highlightedShow differences only (off)
Comparison of MPHB3242, MPHR1362
21 specifications
Design1 differ
PDU typesDiffersMeteredMetered, Switched
Rack capacity0U0U
MountingVerticalVertical
Product colourBlackBlack
Ports & interfaces2 differ
AC outlets quantityDiffers19 AC outlet(s)18 AC outlet(s)
Power plugKnown for oneIEC 60309Unknown — not stated by the source
AC outlet typesC13 coupler, C19 couplerC13 coupler, C19 coupler
Output connectionsDiffers17 x C13 & 2 x C196 x C13 & 12 x C19
Featuresidentical
LED indicatorsYesYes
Management featuresidentical
Management platformWeb, CLI, SNMP, SSH, TelnetWeb, CLI, SNMP, SSH, Telnet
Power2 differ
Nominal input voltageDiffers230 V230-400 V
Maximum currentDiffers16 A32 A
Power protection featuresOver currentOver current
Certificatesidentical
Compliance certificatesRoHSRoHS
CertificationUL, CSA, CE, REACH, FCC Class A, CB, WEEE, ISTAUL, CSA, CE, REACH, FCC Class A, CB, WEEE, ISTA
Operational conditionsidentical
Operating temperature (T-T)0 - 60 °C0 - 60 °C
Storage temperature (T-T)-25 - 85 °C-25 - 85 °C
Operating relative humidity (H-H)5 - 95%5 - 95%
Weight & dimensions1 differ
Width56 mm56 mm
Depth50 mm50 mm
HeightDiffers916.5 mm1736.5 mm

A dash means the value is not stated by the source. Unknown values are never counted for or against a product, and there is no overall score.