Product comparison · 2 power distribution units (pdus)

APC Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 16A, 230V, (21) C13 & (3) C19 vs APC Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 11.0kW, 230V, (21) C13 & (3) C19

Add a product
  • 32specifications compared
  • 8differ
  • 24identical
  • 3known for one product only

Key differences

  • Cable length
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 16A, 230V, (21) C13 & (3) C19:3 m
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 11.0kW, 230V, (21) C13 & (3) C19:1.83 m
  • Nominal input voltage
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 16A, 230V, (21) C13 & (3) C19:200-230 V
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 11.0kW, 230V, (21) C13 & (3) C19:400 V
  • Load capacity
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 16A, 230V, (21) C13 & (3) C19:3680 VA
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 11.0kW, 230V, (21) C13 & (3) C19:11040 VA
  • Maximum power
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 16A, 230V, (21) C13 & (3) C19:3680 W
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 11.0kW, 230V, (21) C13 & (3) C19:11040 W
  • Weight
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 16A, 230V, (21) C13 & (3) C19:6.77 kg
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 11.0kW, 230V, (21) C13 & (3) C19:8.23 kg
  • Package weight
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 16A, 230V, (21) C13 & (3) C19:9.05 kg
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 11.0kW, 230V, (21) C13 & (3) C19:10.5 kg
  • Total carbon footprint (kg of CO2e)
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 16A, 230V, (21) C13 & (3) C19:7441.92
    • Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 11.0kW, 230V, (21) C13 & (3) C19:10364.02

Side by side

Differences highlightedShow differences only (off)
Comparison of AP8659EU3, AP8681
35 specifications
Designidentical
PDU typesMetered, Metered-by-outlet, SwitchedMetered, Metered-by-outlet, Switched
Rack capacity0U0U
MountingVerticalVertical
Product colourBlackBlack
Ports & interfacesidentical
AC outlets quantity24 AC outlet(s)24 AC outlet(s)
Power plugKnown for oneIEC309Unknown — not stated by the source
AC outlet typesC13 coupler, C19 couplerC13 coupler, C19 coupler
Features1 differ
Cable lengthDiffers3 m1.83 m
Management featuresidentical
MonitoringCurrent, Power, VoltageCurrent, Power, Voltage
Outlet controlLock-out, Recycle, Turn off, Turn onLock-out, Recycle, Turn off, Turn on
Power3 differ
Nominal input voltageDiffers200-230 V400 V
AC input frequency50 - 60 Hz50 - 60 Hz
Nominal output voltage230 V230 V
Load capacityDiffers3680 VA11040 VA
Maximum input current per phase16 A16 A
Maximum total current draw per phase16 A16 A
Maximum powerDiffers3680 W11040 W
Maximum currentKnown for oneUnknown — not stated by the source16 A
Certificates1 differ
Compliance certificatesRoHSRoHS
CertificationDiffersEN 55022 A, EN 55024, EN 61000-3-2, EN 61000-3-3, FCC 15 A, ICES-003, PSE, UL, VCCI Class A, VDEEN 55022 A, EN 55024, EN 61000-3-2, EN 61000-3-3, FCC 15 A, ICES-003, UL, VDE
Operational conditionsidentical
Operating temperature (T-T)-5 - 45 °C-5 - 45 °C
Storage temperature (T-T)Known for one-25 - 65 °CUnknown — not stated by the source
Operating relative humidity (H-H)5 - 95%5 - 95%
Storage relative humidity (H-H)5 - 95%5 - 95%
Operating altitude0 - 3000 m0 - 3000 m
Non-operating altitude0 - 15000 m0 - 15000 m
Weight & dimensions1 differ
Width56 mm56 mm
Depth51 mm51 mm
Height1829 mm1829 mm
WeightDiffers6.77 kg8.23 kg
Packaging data1 differ
Package weightDiffers9.05 kg10.5 kg
Package width162 mm162 mm
Package depth117 mm117 mm
Package height2038 mm2038 mm
Logistics data1 differ
Total carbon footprint (kg of CO2e)Differs7441.9210364.02

A dash means the value is not stated by the source. Unknown values are never counted for or against a product, and there is no overall score.