  • PDU types
    • Rack PDU 2G, Metered-by-Outlet, ZeroU, 16A, 100-240V, (21) C13 & (3) C19:Metered, Metered-by-outlet
    • PDPM175G6H power distribution unit (PDU) Black:Modular
  • Nominal input voltage
    • Rack PDU 2G, Metered-by-Outlet, ZeroU, 16A, 100-240V, (21) C13 & (3) C19:200-230 V
    • PDPM175G6H power distribution unit (PDU) Black:480 V
  • AC input frequency
    • Rack PDU 2G, Metered-by-Outlet, ZeroU, 16A, 100-240V, (21) C13 & (3) C19:50 - 60 Hz
    • PDPM175G6H power distribution unit (PDU) Black:60 Hz
  • Maximum current
    • Rack PDU 2G, Metered-by-Outlet, ZeroU, 16A, 100-240V, (21) C13 & (3) C19:20 A
    • PDPM175G6H power distribution unit (PDU) Black:214 A
  • Nominal output voltage
    • Rack PDU 2G, Metered-by-Outlet, ZeroU, 16A, 100-240V, (21) C13 & (3) C19:200-230 V
    • PDPM175G6H power distribution unit (PDU) Black:415 V
  • Load capacity
    • Rack PDU 2G, Metered-by-Outlet, ZeroU, 16A, 100-240V, (21) C13 & (3) C19:3680 VA
    • PDPM175G6H power distribution unit (PDU) Black:175000 VA
  • Operating temperature (T-T)
    • Rack PDU 2G, Metered-by-Outlet, ZeroU, 16A, 100-240V, (21) C13 & (3) C19:-5 - 45 °C
    • PDPM175G6H power distribution unit (PDU) Black:-5 - 40 °C
  • Operating relative humidity (H-H)
    • Rack PDU 2G, Metered-by-Outlet, ZeroU, 16A, 100-240V, (21) C13 & (3) C19:5 - 95%
    • PDPM175G6H power distribution unit (PDU) Black:0 - 95%

Side by side

Differences highlightedShow differences only (off)
Comparison of AP8459WW, PDPM175G6H
35 specifications
Design1 differ
PDU typesDiffersMetered, Metered-by-outletModular
Rack capacityKnown for one0UUnknown — not stated by the source
MountingVerticalVertical
Product colourBlackBlack
Ports & interfacesidentical
AC outlets quantityKnown for one24 AC outlet(s)Unknown — not stated by the source
AC outlet typesKnown for oneC13 coupler, C19 couplerUnknown — not stated by the source
Featuresidentical
LED indicatorsKnown for oneYesUnknown — not stated by the source
Management featuresidentical
MonitoringKnown for oneCurrent, Power, VoltageUnknown — not stated by the source
Power5 differ
Nominal input voltageDiffers200-230 V480 V
AC input frequencyDiffers50 - 60 Hz60 Hz
Maximum currentDiffers20 A214 A
Nominal output voltageDiffers200-230 V415 V
Load capacityDiffers3680 VA175000 VA
Maximum input current per phaseKnown for one16 AUnknown — not stated by the source
Maximum total current draw per phaseKnown for one16 AUnknown — not stated by the source
Maximum powerKnown for one3680 WUnknown — not stated by the source
Output voltageKnown for oneUnknown — not stated by the source208 V
Power protection featuresKnown for oneUnknown — not stated by the sourceOverload
Certificates1 differ
Compliance certificatesKnown for oneRoHSUnknown — not stated by the source
CertificationDiffersEN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3, FCC Part 15 Class A, ICES-003, PSE, UL Listed, VCCI Class A, VDEcUL, CSA, OSHPD, UL 60950-1
Operational conditions3 differ
Operating temperature (T-T)Differs-5 - 45 °C-5 - 40 °C
Storage temperature (T-T)-25 - 65 °C-25 - 65 °C
Operating relative humidity (H-H)Differs5 - 95%0 - 95%
Storage relative humidity (H-H)Differs5 - 95%0 - 95%
Non-operating altitude0 - 15000 m0 - 15000 m
Operating altitudeKnown for oneUnknown — not stated by the source0 - 2952.6 m
Weight & dimensions4 differ
WidthDiffers56 mm600 mm
DepthDiffers51 mm1069 mm
HeightDiffers1829 mm2007 mm
WeightDiffers5.08 kg941 kg
Packaging data4 differ
Package weightDiffers8.35 kg987 kg
Package widthDiffers163 mm1016 mm
Package depthDiffers117 mm1219 mm
Package heightDiffers2037 mm2153 mm
Logistics dataidentical
Total carbon footprint (kg of CO2e)Known for one4728.07Unknown — not stated by the source