Product comparison · 2 power distribution units (pdus)

APC Rack PDU, Switched, 2U, 30A vs APC AP8966 power distribution unit (PDU) 32 AC outlet(s) 0U Black

Add a product
  • 28specifications compared
  • 21differ
  • 7identical
  • 9known for one product only

Key differences

  • Rack capacity
    • Rack PDU, Switched, 2U, 30A:2U
    • AP8966 power distribution unit (PDU) 32 AC outlet(s) 0U Black:0U
  • AC outlets quantity
    • Rack PDU, Switched, 2U, 30A:16 AC outlet(s)
    • AP8966 power distribution unit (PDU) 32 AC outlet(s) 0U Black:32 AC outlet(s)
  • AC outlet types
    • Rack PDU, Switched, 2U, 30A:NEMA 5–20R
    • AP8966 power distribution unit (PDU) 32 AC outlet(s) 0U Black:C13 coupler, C19 coupler
  • LED indicators
    • Rack PDU, Switched, 2U, 30A:Alarm
    • AP8966 power distribution unit (PDU) 32 AC outlet(s) 0U Black:Yes
  • Cable length
    • Rack PDU, Switched, 2U, 30A:3.05 m
    • AP8966 power distribution unit (PDU) 32 AC outlet(s) 0U Black:1.83 m
  • Nominal input voltage
    • Rack PDU, Switched, 2U, 30A:100-120 V
    • AP8966 power distribution unit (PDU) 32 AC outlet(s) 0U Black:208 V
  • Maximum current
    • Rack PDU, Switched, 2U, 30A:30 A
    • AP8966 power distribution unit (PDU) 32 AC outlet(s) 0U Black:60 A
  • Nominal output voltage
    • Rack PDU, Switched, 2U, 30A:120 V
    • AP8966 power distribution unit (PDU) 32 AC outlet(s) 0U Black:208 V

Side by side

Differences highlightedShow differences only (off)
Comparison of AP7902B, AP8966
37 specifications
Design1 differ
PDU typesSwitchedSwitched
Rack capacityDiffers2U0U
MountingKnown for oneUnknown — not stated by the sourceHorizontal/Vertical
Product colourBlackBlack
Ports & interfaces2 differ
AC outlets quantityDiffers16 AC outlet(s)32 AC outlet(s)
Power plugKnown for oneUnknown — not stated by the sourceIEC 60309
AC outlet typesDiffersNEMA 5–20RC13 coupler, C19 coupler
Input connection typeKnown for oneNEMA L5-30PUnknown — not stated by the source
Output connectionsKnown for oneNEMA 5-20RUnknown — not stated by the source
Features2 differ
LED indicatorsDiffersAlarmYes
Cable lengthDiffers3.05 m1.83 m
Management featuresidentical
MonitoringKnown for oneUnknown — not stated by the sourceCurrent
Outlet controlKnown for oneRecycle, Turn offUnknown — not stated by the source
Power5 differ
Nominal input voltageDiffers100-120 V208 V
AC input frequency50 - 60 Hz50 - 60 Hz
Maximum currentDiffers30 A60 A
Nominal output voltageDiffers120 V208 V
Load capacityDiffers2880 VA17300 VA
Maximum input current per phaseKnown for oneUnknown — not stated by the source48 A
Maximum total current draw per phaseDiffers30 A48 A
Power protection featuresKnown for oneUnknown — not stated by the sourceOverload
Certificates1 differ
Compliance certificatesRoHSRoHS
CertificationDifferscUL Listed, CSA, FCC Part 15 Class A, ICES-003, Industry Canada, UL 60950, UL ListedcUL Listed, EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3, FCC Part 15 Class A, ICES-003, UL Listed, VCCI Class A, REACH, PEP, EOLI
Operational conditions2 differ
Operating temperature (T-T)0 - 45 °C0 - 45 °C
Storage temperature (T-T)-25 - 65 °C-25 - 65 °C
Operating relative humidity (H-H)Differs0 - 95%5 - 95%
Storage relative humidity (H-H)Differs0 - 95%5 - 95%
Operating altitude0 - 3000 m0 - 3000 m
Non-operating altitudeKnown for oneUnknown — not stated by the source0 - 15000 m
Weight & dimensions4 differ
WidthDiffers445 mm56 mm
DepthDiffers114 mm51 mm
HeightDiffers89 mm1829 mm
WeightDiffers4.5 kg15.9 kg
Packaging data4 differ
Package weightDiffers6.55 kg20 kg
Package widthDiffers508 mm221 mm
Package depthDiffers368 mm112 mm
Package heightDiffers140 mm2149 mm

A dash means the value is not stated by the source. Unknown values are never counted for or against a product, and there is no overall score.