Product comparison · 2 uninterruptible power supplies (upss)

Salicru SLC-6000-TWIN PRO2 B1 vs Salicru SLC-10000-TWIN/3 PRO2 B1

Add a product
  • 63specifications compared
  • 15differ
  • 48identical
  • 6known for one product only

Key differences

The Salicru SLC-10000-TWIN/3 PRO2 B1 has 4 kVA more output power capacity than the Salicru SLC-6000-TWIN PRO2 B1 (10 kVA vs 6 kVA). The Salicru SLC-10000-TWIN/3 PRO2 B1 has 3,000 W more output power than the Salicru SLC-6000-TWIN PRO2 B1 (9000 W vs 6000 W). The Salicru SLC-10000-TWIN/3 PRO2 B1 has 80 V more input operation voltage (min) than the Salicru SLC-6000-TWIN PRO2 B1 (190 V vs 110 V). Safety: EN-IEC 62040-1; EN-IEC 60950-1 on the Salicru SLC-6000-TWIN PRO2 B1, EN 62040-1; EN 60950-1 on the Salicru SLC-10000-TWIN/3 PRO2 B1.

  • Output power capacity
    • SLC-6000-TWIN PRO2 B1:6 kVA
    • SLC-10000-TWIN/3 PRO2 B1:10 kVA
  • Output power
    • SLC-6000-TWIN PRO2 B1:6000 W
    • SLC-10000-TWIN/3 PRO2 B1:9000 W
  • Input operation voltage (min)
    • SLC-6000-TWIN PRO2 B1:110 V
    • SLC-10000-TWIN/3 PRO2 B1:190 V
  • Input operation voltage (max)
    • SLC-6000-TWIN PRO2 B1:276 V
    • SLC-10000-TWIN/3 PRO2 B1:478 V
  • Number of input phases
    • SLC-6000-TWIN PRO2 B1:1
    • SLC-10000-TWIN/3 PRO2 B1:3
  • Efficiency
    • SLC-6000-TWIN PRO2 B1:94%
    • SLC-10000-TWIN/3 PRO2 B1:90%
  • Output power factor
    • SLC-6000-TWIN PRO2 B1:1
    • SLC-10000-TWIN/3 PRO2 B1:0.9
  • Output voltage Total Harmonic Distortion (THD)
    • SLC-6000-TWIN PRO2 B1:4%
    • SLC-10000-TWIN/3 PRO2 B1:5%

Side by side

Differences highlightedShow differences only (off)
Comparison of 699CB000008, 699CC000006
69 specifications
A

Salicru

SLC-6000-TWIN PRO2 B1

Model 699CB000008

View product
B

Salicru

SLC-10000-TWIN/3 PRO2 B1

Model 699CC000006

View product
Features12 differ
UPS topologyDouble-conversion (Online)Double-conversion (Online)
Output power capacityDiffers6 kVA10 kVA
Output powerDiffers6000 W9000 W
Input operation voltage (min)Differs110 V190 V
Input operation voltage (max)Differs276 V478 V
Input frequency50/60 Hz50/60 Hz
Output operation voltage (min)208 V208 V
Output operation voltage (max)240 V240 V
Output frequency regulation4 Hz4 Hz
Output voltage regulation1%1%
Number of input phasesDiffers13
Number of output phases11
EfficiencyDiffers94%90%
Input power factor0.990.99
Output power factorDiffers10.9
Crest factor3:13:1
ECO modeYesYes
Emergency Power Off (EPO)YesYes
Overload capacity (10 minutes)110%110%
Overload capacity (1 minute)130%130%
Output voltage Total Harmonic Distortion (THD)Differs4%5%
Input current Total Harmonic Distortion (THD)Differs4%5%
Total Harmonic Distortion (THD) (linear load)Differs1%2%
Total Harmonic Distortion (THD) (non-linear load)Differs4%5%
Noise level60 dB60 dB
Surge protectionYesYes
Power protection featuresUnder voltageUnder voltage
Maximum number of paralleling UPSs33
Synchronisation with mains4 Hz4 Hz
Synchronisation without mainsDiffers0.1 Hz0.05 Hz
Temperature voltage compensationYesYes
Maintenance-freeYesYes
Input frequency converterKnown for oneUnknown — not stated by the sourceYes
Ports & interfacesidentical
AC outlet typesC13 couplerC13 coupler
AC outlets quantity2 AC outlet(s)2 AC outlet(s)
Number of output IEC jumpers22
USB portYesYes
USB 2.0 ports quantity11
Serial interfaceYesYes
Serial interface typeRS-232RS-232
RS-232 ports11
Parallel ports quantity33
Emergency Power Off (EPO) connectorYesYes
Batteryidentical
Battery technologyLead-Calcium (Pb-Ca)Lead-Calcium (Pb-Ca)
Battery recharge timeKnown for one7 hUnknown — not stated by the source
Hot-swap batteryKnown for oneYesUnknown — not stated by the source
Automatic battery testYesYes
Off-mode chargingKnown for oneYesUnknown — not stated by the source
Battery recharge time(90%)Known for oneUnknown — not stated by the source9 h
Cold startKnown for oneUnknown — not stated by the sourceYes
Designidentical
Form factorTowerTower
Product colourBlackBlack
Cooling typeActiveActive
Built-in fanYesYes
Display typeLCDLCD
LED indicatorsYesYes
Operational conditionsidentical
Operating temperature (T-T)0 - 40 °C0 - 40 °C
Operating relative humidity (H-H)0 - 95%0 - 95%
Operating altitude0 - 5000 m0 - 5000 m
Safety regulation & standards1 differ
SafetyDiffersEN-IEC 62040-1; EN-IEC 60950-1EN 62040-1; EN 60950-1
Certificates1 differ
CertificationDiffersEN-IEC 62040-2 CE ISO 9001, ISO 140001EN 62040-2 C3 EN 62040-3 ISO-9001 ISO-14001
Weight & dimensions1 differ
Width250 mm250 mm
Depth592 mm592 mm
Height576 mm576 mm
WeightDiffers26.5 kg29 kg
Logistics dataidentical
Harmonized System (HS) code8507800085078000
Other featuresidentical
Battery typeAGMAGM
BypassHybrid, NillHybrid, Nill
I/O portsIntelligent slotIntelligent slot

A dash means the value is not stated by the source. Unknown values are never counted for or against a product, and there is no overall score.

More uninterruptible power supplies (upss) comparisons