Product comparison · 2 uninterruptible power supplies (upss)

CyberPower OL8KRT uninterruptible power supply (UPS) Double-conversion (Online) 8 kVA vs CyberPower UT700EG uninterruptible power supply (UPS) Line-Interactive 0.7 kVA

Add a product
  • 31specifications compared
  • 20differ
  • 11identical
  • 42known for one product only

Key differences

  • UPS topology
    • OL8KRT uninterruptible power supply (UPS) Double-conversion (Online) 8 kVA:Double-conversion (Online)
    • UT700EG uninterruptible power supply (UPS) Line-Interactive 0.7 kVA:Line-Interactive
  • Output power capacity
    • OL8KRT uninterruptible power supply (UPS) Double-conversion (Online) 8 kVA:8 kVA
    • UT700EG uninterruptible power supply (UPS) Line-Interactive 0.7 kVA:0.7 kVA
  • Output power
    • OL8KRT uninterruptible power supply (UPS) Double-conversion (Online) 8 kVA:8000 W
    • UT700EG uninterruptible power supply (UPS) Line-Interactive 0.7 kVA:400 W
  • Input operation voltage (min)
    • OL8KRT uninterruptible power supply (UPS) Double-conversion (Online) 8 kVA:120 V
    • UT700EG uninterruptible power supply (UPS) Line-Interactive 0.7 kVA:165 V
  • Input operation voltage (max)
    • OL8KRT uninterruptible power supply (UPS) Double-conversion (Online) 8 kVA:280 V
    • UT700EG uninterruptible power supply (UPS) Line-Interactive 0.7 kVA:290 V
  • Input frequency
    • OL8KRT uninterruptible power supply (UPS) Double-conversion (Online) 8 kVA:40 - 70 Hz
    • UT700EG uninterruptible power supply (UPS) Line-Interactive 0.7 kVA:50/60 Hz
  • Output operation voltage (max)
    • OL8KRT uninterruptible power supply (UPS) Double-conversion (Online) 8 kVA:240 V
    • UT700EG uninterruptible power supply (UPS) Line-Interactive 0.7 kVA:230 V
  • Surge energy rating
    • OL8KRT uninterruptible power supply (UPS) Double-conversion (Online) 8 kVA:2430 J
    • UT700EG uninterruptible power supply (UPS) Line-Interactive 0.7 kVA:125 J

Side by side

Differences highlightedShow differences only (on)
Comparison of OL8KRT, UT700EG
73 specifications
Features10 differ
UPS topologyDiffersDouble-conversion (Online)Line-Interactive
Output power capacityDiffers8 kVA0.7 kVA
Output powerDiffers8000 W400 W
Input operation voltage (min)Differs120 V165 V
Input operation voltage (max)Differs280 V290 V
Input frequencyDiffers40 - 70 Hz50/60 Hz
Output operation voltage (min)Known for one200 VUnknown — not stated by the source
Output operation voltage (max)Differs240 V230 V
Output frequencyKnown for one50/60 HzUnknown — not stated by the source
Surge energy ratingDiffers2430 J125 J
Transfer time (Line Mode to Battery Mode)Differs0 ms4 ms
Efficiency (ECO mode)Known for one96%Unknown — not stated by the source
Input power factorKnown for one0.99Unknown — not stated by the source
Output power factorKnown for one1Unknown — not stated by the source
Crest factorKnown for one3:1Unknown — not stated by the source
ECO modeKnown for oneYesUnknown — not stated by the source
Emergency Power Off (EPO)Known for oneYesUnknown — not stated by the source
Overload capacity (1 minute)Known for one125%Unknown — not stated by the source
Overload capacity (10 seconds)Known for one130%Unknown — not stated by the source
Noise levelKnown for one65 dBUnknown — not stated by the source
Power protection featuresDiffersOverload, Short circuitOverload
Audible alarm(s)Known for oneYesUnknown — not stated by the source
Audible alarm modesKnown for oneAlarm when on battery, Fault, Low battery alarm, Overload alarmUnknown — not stated by the source
Automatic Voltage Regulation (AVR)Known for oneUnknown — not stated by the sourceYes
Number of input phasesKnown for oneUnknown — not stated by the source1
Ports & interfaces1 differ
AC outlet typesDiffersNEMA L6-30R, TerminalType F
AC outlets quantityKnown for one4 AC outlet(s)Unknown — not stated by the source
USB portKnown for oneYesUnknown — not stated by the source
USB 2.0 ports quantityKnown for one1Unknown — not stated by the source
USB port typeKnown for oneUSB Type-BUnknown — not stated by the source
Serial interfaceKnown for oneYesUnknown — not stated by the source
Serial interface typeKnown for oneRS-232Unknown — not stated by the source
RS-232 portsKnown for one1Unknown — not stated by the source
Modem (RJ-11) portsKnown for one2Unknown — not stated by the source
Emergency Power Off (EPO) connectorKnown for oneYesUnknown — not stated by the source
Number of type F outputsKnown for oneUnknown — not stated by the source3
Battery1 differ
Battery capacityDiffers9 Ah6 Ah
Number of batteries supportedKnown for one20Unknown — not stated by the source
Typical backup time at full loadKnown for one4.7 minUnknown — not stated by the source
Typical backup time at half loadKnown for one12 minUnknown — not stated by the source
Battery recharge time(90%)Known for one5 hUnknown — not stated by the source
Hot-swap batteryKnown for oneYesUnknown — not stated by the source
Cold startKnown for oneYesUnknown — not stated by the source
Charging currentKnown for oneUnknown — not stated by the source1.74 A
Design2 differ
Form factorDiffersRackmount/TowerTower
Housing materialDiffersSteelPlastic
Rack capacityKnown for one6UUnknown — not stated by the source
Display typeKnown for oneLCDUnknown — not stated by the source
Cable lengthKnown for oneUnknown — not stated by the source1.4 m
Operational conditions2 differ
Storage temperature (T-T)Differs-20 - 45 °C-20 - 50 °C
Storage relative humidity (H-H)Differs0 - 95%0 - 90%
Non-operating altitudeKnown for one0 - 15000 mUnknown — not stated by the source
Packaging contentidentical
Rack mount kitKnown for oneYesUnknown — not stated by the source
Cables includedKnown for onePhone (RJ-11), Serial, USB cableUnknown — not stated by the source
Quick installation guideKnown for oneYesUnknown — not stated by the source
Certificatesidentical
CertificationKnown for oneUnknown — not stated by the sourceCE
Safety regulation & standardsidentical
SafetyKnown for oneUL 1778 5th Ed., CSA C22.2 NO.107.3-05, FCC 5 AUnknown — not stated by the source
Weight & dimensions4 differ
WidthDiffers433 mm84 mm
DepthDiffers660 mm280 mm
HeightDiffers266 mm174 mm
WeightDiffers103 kg4.2 kg
Packaging dataidentical
Rubber feetKnown for oneYesUnknown — not stated by the source

A dash means the value is not stated by the source. Unknown values are never counted for or against a product, and there is no overall score.