Product comparison · 2 uninterruptible power supplies (upss)

APC G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA vs APC MGE Galaxy 3500, 15kVA

Add a product
  • 35specifications compared
  • 26differ
  • 9identical
  • 15known for one product only

Key differences

The APC G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA has 45 kVA more output power capacity than the APC MGE Galaxy 3500, 15kVA (60 kVA vs 15 kVA). The APC G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA has 42,000 W more output power than the APC MGE Galaxy 3500, 15kVA (54000 W vs 12000 W). The APC MGE Galaxy 3500, 15kVA has 17 V more input operation voltage (min) than the APC G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA (340 V vs 323 V). Input frequency: 45/65 Hz on the APC G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA, 40 - 70 Hz on the APC MGE Galaxy 3500, 15kVA. Product colour: Black on the APC G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA, Black, Silver on the APC MGE Galaxy 3500, 15kVA.

  • Output power capacity
    • G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA:60 kVA
    • MGE Galaxy 3500, 15kVA:15 kVA
  • Output power
    • G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA:54000 W
    • MGE Galaxy 3500, 15kVA:12000 W
  • Input operation voltage (min)
    • G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA:323 V
    • MGE Galaxy 3500, 15kVA:340 V
  • Input operation voltage (max)
    • G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA:477 V
    • MGE Galaxy 3500, 15kVA:460 V
  • Input frequency
    • G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA:45/65 Hz
    • MGE Galaxy 3500, 15kVA:40 - 70 Hz
  • Output operation voltage (min)
    • G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA:400 V
    • MGE Galaxy 3500, 15kVA:220 V
  • Output operation voltage (max)
    • G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA:415 V
    • MGE Galaxy 3500, 15kVA:240 V
  • Maximum current
    • G55TUPM60HXS uninterruptible power supply (UPS) Double-conversion (Online) 60 kVA:240 A
    • MGE Galaxy 3500, 15kVA:20 A

Side by side

Differences highlightedShow differences only (off)
Comparison of G55TUPM60HXS, MGE Galaxy 3500, 15kVA
50 specifications
Features12 differ
UPS topologyDouble-conversion (Online)Double-conversion (Online)
Output power capacityDiffers60 kVA15 kVA
Output powerDiffers54000 W12000 W
WaveformSineSine
Input operation voltage (min)Differs323 V340 V
Input operation voltage (max)Differs477 V460 V
Input frequencyDiffers45/65 Hz40 - 70 Hz
Output operation voltage (min)Differs400 V220 V
Output operation voltage (max)Differs415 V240 V
Output frequencyKnown for one50 HzUnknown — not stated by the source
Maximum currentDiffers240 A20 A
EfficiencyDiffers92%95.5%
Input power factorDiffers10.98
Crest factorKnown for one3:1Unknown — not stated by the source
Emergency Power Off (EPO)YesYes
Output voltage Total Harmonic Distortion (THD)Differs2.5%5%
Input current Total Harmonic Distortion (THD)5%5%
Noise levelDiffers65 dB51.3 dB
Auto-restartKnown for oneYesUnknown — not stated by the source
Number of input phasesKnown for oneUnknown — not stated by the source3
Audible alarm(s)Known for oneUnknown — not stated by the sourceYes
Ports & interfacesidentical
Power plugKnown for oneTerminalUnknown — not stated by the source
AC outlet typesKnown for oneUnknown — not stated by the sourceTerminal
Serial interfaceKnown for oneUnknown — not stated by the sourceYes
Serial interface typeKnown for oneUnknown — not stated by the sourceRS-232
RS-232 portsKnown for oneUnknown — not stated by the source1
Batteryidentical
Battery life (max)Known for one10 year(s)Unknown — not stated by the source
Hot-swap batteryKnown for oneYesUnknown — not stated by the source
Automatic battery testKnown for oneYesUnknown — not stated by the source
Design2 differ
Form factorTowerTower
Product colourDiffersBlackBlack, Silver
Display typeLCDLCD
LED indicatorsKnown for oneYesUnknown — not stated by the source
International Protection (IP) codeDiffersIP20, IP32IP51
Operational conditions3 differ
Operating temperature (T-T)0 - 40 °C0 - 40 °C
Storage temperature (T-T)Differs-20 - 45 °C0 - 40 °C
Operating relative humidity (H-H)0 - 95%0 - 95%
Storage relative humidity (H-H)0 - 95%0 - 95%
Operating altitudeDiffers0 - 1000 m0 - 999.9 m
Non-operating altitudeDiffers0 - 12000 m0 - 15000 m
Certificates1 differ
CertificationDiffersCE, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, ISO 9001, TUV, VDECE, EN 50091-2, EN/IEC 62040-3, IEC 61000-3-2, IEC 61000-3-3, ISO 14001, ISO 9001, VFI-SS-111
Weight & dimensions4 differ
WidthDiffers712 mm523 mm
DepthDiffers855 mm838 mm
HeightDiffers2180 mm1491 mm
WeightDiffers456 kg261 kg
Packaging data4 differ
Package widthDiffers1080 mm650 mm
Package depthDiffers1200 mm1062 mm
Package heightDiffers2300 mm1643 mm
Package weightDiffers480 kg290 kg
Packaging contentidentical
ManualKnown for oneUnknown — not stated by the sourceYes

A dash means the value is not stated by the source. Unknown values are never counted for or against a product, and there is no overall score.