Product comparison · 2 uninterruptible power supplies (upss)

APC G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA vs APC Image MGE Galaxy 5500

Add a product
  • 39specifications compared
  • 10differ
  • 29identical
  • 13known for one product only

Key differences

The APC Image MGE Galaxy 5500 has 20 kVA more output power capacity than the APC G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA (40 kVA vs 20 kVA). The APC Image MGE Galaxy 5500 has 18,000 W more output power than the APC G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA (36000 W vs 18000 W). The APC Image MGE Galaxy 5500 has 17 V more input operation voltage (min) than the APC G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA (340 V vs 323 V). International Protection (IP) code: IP32 on the APC G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA, IP22 on the APC Image MGE Galaxy 5500. Operating altitude: 0 - 1000 m on the APC G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA, 0 - 999.9 m on the APC Image MGE Galaxy 5500.

  • Output power capacity
    • G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:20 kVA
    • Image MGE Galaxy 5500:40 kVA
  • Output power
    • G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:18000 W
    • Image MGE Galaxy 5500:36000 W
  • Input operation voltage (min)
    • G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:323 V
    • Image MGE Galaxy 5500:340 V
  • Input operation voltage (max)
    • G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:477 V
    • Image MGE Galaxy 5500:460 V
  • Maximum current
    • G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:190 A
    • Image MGE Galaxy 5500:77 A
  • Efficiency
    • G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:87%
    • Image MGE Galaxy 5500:91%
  • International Protection (IP) code
    • G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:IP32
    • Image MGE Galaxy 5500:IP22
  • Operating altitude
    • G55TUPM20HMS uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:0 - 1000 m
    • Image MGE Galaxy 5500:0 - 999.9 m

Side by side

Differences highlightedShow differences only (off)
Comparison of G55TUPM20HMS, Image MGE Galaxy 5500
52 specifications
Features6 differ
UPS topologyDouble-conversion (Online)Double-conversion (Online)
Output power capacityDiffers20 kVA40 kVA
Output powerDiffers18000 W36000 W
WaveformSineSine
Input operation voltage (min)Differs323 V340 V
Input operation voltage (max)Differs477 V460 V
Input frequency45/65 Hz45/65 Hz
Output operation voltage (min)380 V380 V
Output operation voltage (max)415 V415 V
Output frequencyKnown for one50 HzUnknown — not stated by the source
Maximum currentDiffers190 A77 A
EfficiencyDiffers87%91%
Input power factor11
Crest factor3:13:1
Emergency Power Off (EPO)YesYes
Output voltage Total Harmonic Distortion (THD)2.5%2.5%
Noise level65 dB65 dB
Auto-restartKnown for oneYesUnknown — not stated by the source
Number of input phasesKnown for oneUnknown — not stated by the source3
Number of output phasesKnown for oneUnknown — not stated by the source3
Ports & interfacesidentical
Power plugTerminalTerminal
Serial interfaceKnown for oneYesUnknown — not stated by the source
SmartSlotYesYes
Emergency Power Off (EPO) connectorKnown for oneUnknown — not stated by the sourceYes
Batteryidentical
Battery life (max)10 year(s)10 year(s)
Hot-swap batteryKnown for oneYesUnknown — not stated by the source
Automatic battery testKnown for oneYesUnknown — not stated by the source
Design1 differ
Form factorTowerTower
Product colourGreyGrey
Display typeLCDLCD
LED indicatorsYesYes
International Protection (IP) codeDiffersIP32IP22
Operational conditions2 differ
Operating temperature (T-T)0 - 40 °C0 - 40 °C
Storage temperature (T-T)-20 - 45 °C-20 - 45 °C
Operating relative humidity (H-H)0 - 95%0 - 95%
Storage relative humidity (H-H)0 - 95%0 - 95%
Operating altitudeDiffers0 - 1000 m0 - 999.9 m
Non-operating altitudeDiffers0 - 3600 m0 - 12000 m
Packaging contentidentical
ManualKnown for oneYesUnknown — not stated by the source
Quick installation guideKnown for oneYesUnknown — not stated by the source
Certificates1 differ
CertificationDiffersCE, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, IEC 62040-2, ISO 9001, TÜV, VDECE, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, IEC 62040-2, ISO 9001, TUV, VDE
Compliance certificatesKnown for oneUnknown — not stated by the sourceRoHS
Weight & dimensionsidentical
Width712 mm712 mm
Depth855 mm855 mm
Height2210 mm2210 mm
Weight488 kg488 kg
Packaging dataidentical
Package width1080 mm1080 mm
Package depth1200 mm1200 mm
Package height2340 mm2340 mm
Package weight510 kg510 kg
Other featuresidentical
Type of input protection requiredKnown for oneUnknown — not stated by the sourcegL fuse
BypassKnown for oneUnknown — not stated by the sourceBuilt-in Maintenance Bypass, Built-in Static Bypass, Optional External Bypass

A dash means the value is not stated by the source. Unknown values are never counted for or against a product, and there is no overall score.

More uninterruptible power supplies (upss) comparisons

All uninterruptible power supplies (upss) comparisons