Product comparison · 2 uninterruptible power supplies (upss)

APC G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA vs APC G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA

Add a product
  • 39specifications compared
  • 24differ
  • 15identical
  • 10known for one product only

Key differences

The APC G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA has 2,000 W more output power than the APC G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA (18000 W vs 16000 W). The APC G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA has 57 V more input operation voltage (min) than the APC G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA (380 V vs 323 V). The APC G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA has 62 V more input operation voltage (max) than the APC G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA (477 V vs 415 V). AC outlet types: Hard Wire 5-wire (3PH + N + G) on the APC G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA, Hard Wire 4-wire (3PH + G) on the APC G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA. Battery life (max): 5 year(s) on the APC G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA, 10 year(s) on the APC G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA.

  • Output power
    • G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:16000 W
    • G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:18000 W
  • Input operation voltage (min)
    • G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:323 V
    • G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:380 V
  • Input operation voltage (max)
    • G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:477 V
    • G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:415 V
  • Output operation voltage (min)
    • G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:220 V
    • G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:380 V
  • Output operation voltage (max)
    • G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:240 V
    • G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:415 V
  • Maximum current
    • G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:130 A
    • G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:190 A
  • Output voltage Total Harmonic Distortion (THD)
    • G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:5%
    • G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:2%
  • Input current Total Harmonic Distortion (THD)
    • G3HT20K3IB2S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:5%
    • G55TUPSM20HB30S uninterruptible power supply (UPS) Double-conversion (Online) 20 kVA:3%

Side by side

Differences highlightedShow differences only (on)
Comparison of G3HT20K3IB2S, G55TUPSM20HB30S
49 specifications
Features9 differ
Output powerDiffers16000 W18000 W
Input operation voltage (min)Differs323 V380 V
Input operation voltage (max)Differs477 V415 V
Output operation voltage (min)Differs220 V380 V
Output operation voltage (max)Differs240 V415 V
Maximum currentDiffers130 A190 A
EfficiencyKnown for oneUnknown — not stated by the source91.4%
Output voltage Total Harmonic Distortion (THD)Differs5%2%
Input current Total Harmonic Distortion (THD)Differs5%3%
Noise levelDiffers53.6 dB55.5 dB
Input power factorKnown for one0.99Unknown — not stated by the source
Power protection featuresKnown for oneOverloadUnknown — not stated by the source
Web-based managementKnown for oneYesUnknown — not stated by the source
Ports & interfaces1 differ
AC outlet typesDiffersHard Wire 5-wire (3PH + N + G)Hard Wire 4-wire (3PH + G)
Power plugKnown for oneUnknown — not stated by the sourceTerminal
AC outlets quantityKnown for oneUnknown — not stated by the source1 AC outlet(s)
Battery1 differ
Battery voltageKnown for oneUnknown — not stated by the source432 V
Battery life (max)Differs5 year(s)10 year(s)
Battery recharge timeKnown for oneUnknown — not stated by the source10 h
Designidentical
LED indicatorsKnown for oneUnknown — not stated by the sourceYes
Operational conditions4 differ
Operating temperature (T-T)Differs0 - 35 °C0 - 40 °C
Storage temperature (T-T)Differs-10 - 60 °C-20 - 45 °C
Operating altitudeDiffers0 - 3000 m0 - 1000 m
Non-operating altitudeDiffers0 - 9000 m0 - 12000 m
Certificates1 differ
CertificationDiffersCE, EN/IEC 62040-1-1, EN/IEC 62040-2, EN/IEC 62040-3, IEC 61000-4-5, IEC 62040-2, TUV, VFI-SS-111CE, EN/IEC 62040-3, IEC 62040-1-2, IEC 62040-2, ISO 9001, TUV, VDE
Compliance certificatesKnown for oneRoHSUnknown — not stated by the source
Weight & dimensions4 differ
WidthDiffers500 mm1110 mm
DepthDiffers950 mm850 mm
HeightDiffers1300 mm1900 mm
WeightDiffers430 kg888 kg
Packaging data4 differ
Package widthDiffers800 mm1130 mm
Package depthDiffers965 mm960 mm
Package heightDiffers1440 mm2030 mm
Package weightDiffers456 kg1065 kg

A dash means the value is not stated by the source. Unknown values are never counted for or against a product, and there is no overall score.