Product comparison · 2 power distribution units (pdus)

APC NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet vs StarTech.com 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets

Add a product
  • 20specifications compared
  • 19differ
  • 1identical
  • 31known for one product only

Key differences

The StarTech.com 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets has 1 U more rack capacity than the APC NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet (1U vs 0U). The APC NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet has 0.6 m more cable length than the StarTech.com 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets (3 m vs 2.4 m). The APC NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet has 45 A more maximum current than the StarTech.com 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets (60 A vs 15 A). PDU types: Metered on the APC NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet, Basic on the StarTech.com 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets. AC outlets quantity: 42 AC outlet(s) on the APC NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet, 14 AC outlet(s) on the StarTech.com 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets.

  • PDU types
    • NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet:Metered
    • 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets:Basic
  • Rack capacity
    • NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet:0U
    • 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets:1U
  • AC outlets quantity
    • NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet:42 AC outlet(s)
    • 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets:14 AC outlet(s)
  • Cable length
    • NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet:3 m
    • 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets:2.4 m
  • Nominal input voltage
    • NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet:415 3 phases
    • 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets:120 V
  • Maximum current
    • NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet:60 A
    • 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets:15 A
  • Nominal output voltage
    • NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet:400 V
    • 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets:120 V
  • Output voltage
    • NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet:240 V
    • 14-Outlet Rackmount PDU, 1U Server Power Strip with 6x Front and 8x Rear Ports, Mounted Power Distribution Unit for 19-Inch Racks and Cabinets:125 V

Side by side

Differences highlightedShow differences only (on)
Comparison of NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V 63A or 34.6kW 415V 60A, 560P6, 42 Outlet, 1415B8H-RACK-PDU-SP
51 specifications
Design2 differ
PDU typesDiffersMeteredBasic
TypeKnown for oneThree-phaseUnknown — not stated by the source
Rack capacityDiffers0U1U
Housing materialKnown for oneUnknown — not stated by the sourceSteel
On/off switchKnown for oneUnknown — not stated by the sourceYes
Ports & interfaces2 differ
AC outlets quantityDiffers42 AC outlet(s)14 AC outlet(s)
AC outlet typesDiffersC13 coupler, C15 coupler, C19 coupler, C21 couplerNEMA 5-15R
Ethernet LAN (RJ-45) portsKnown for one5Unknown — not stated by the source
USB ports quantityKnown for one1Unknown — not stated by the source
Input connection typeKnown for oneIEC 60309 60 A 3P + N + PEUnknown — not stated by the source
Power plugKnown for oneUnknown — not stated by the sourceNEMA 5-15P
Features1 differ
Cable lengthDiffers3 m2.4 m
Management featuresidentical
Management platformKnown for oneNMC3Unknown — not stated by the source
Power5 differ
Nominal input voltageDiffers415 3 phases120 V
AC input frequencyKnown for one50/60 HzUnknown — not stated by the source
Maximum currentDiffers60 A15 A
Nominal output voltageDiffers400 V120 V
Output voltageDiffers240 V125 V
Load capacityDiffers34600 VA1500 VA
Number of phasesKnown for one3Unknown — not stated by the source
Battery replacement accessibilityKnown for oneNon-removableUnknown — not stated by the source
Maximum total current draw per phaseKnown for oneUnknown — not stated by the source15 A
Circuit breakerKnown for oneUnknown — not stated by the sourceYes
Certificates1 differ
Compliance certificatesDiffersRoHS, REACH, WEEERoHS, Trade Agreements Act (TAA)
Waste Electrical and Electronic Equipment (WEEE) complianceKnown for oneYesUnknown — not stated by the source
Weight & dimensions4 differ
WidthDiffers56 mm95.2 mm
DepthDiffers75 mm462.5 mm
HeightDiffers1826 mm43.3 mm
WeightDiffers11.7 kg1.62 kg
Packaging data4 differ
Package weightDiffers17 kg2.6 kg
Package widthDiffers132 mm185 mm
Package depthDiffers262 mm552 mm
Package heightDiffers2110 mm80 mm
Technical detailsidentical
Preferred mounting positionKnown for oneno preferenceUnknown — not stated by the source
Removable batteryKnown for oneNoUnknown — not stated by the source
Packaging without single use plasticKnown for oneNoUnknown — not stated by the source
SCIP numberKnown for one31346aed-552c-4a16-81d9-e683a383b6daUnknown — not stated by the source
Sustainable packagingKnown for oneNoUnknown — not stated by the source
Take-back systemKnown for oneNoUnknown — not stated by the source
Logistics dataidentical
Customs product code (TARIC)Known for one8537109899Unknown — not stated by the source
Master (outer) case widthKnown for oneUnknown — not stated by the source570 mm
Master (outer) case lengthKnown for oneUnknown — not stated by the source206 mm
Master (outer) case heightKnown for oneUnknown — not stated by the source352 mm
Products per master (outer) caseKnown for oneUnknown — not stated by the source4 pc(s)
Packaging contentidentical
ManualKnown for oneUnknown — not stated by the sourceYes
Number of screw nutsKnown for oneUnknown — not stated by the source4
Number of screwsKnown for oneUnknown — not stated by the source4
Rack mount kitKnown for oneUnknown — not stated by the sourceYes
Screw nuts includedKnown for oneUnknown — not stated by the sourceYes
Screws includedKnown for oneUnknown — not stated by the sourceYes

A dash means the value is not stated by the source. Unknown values are never counted for or against a product, and there is no overall score.